Wire size calculator

Pick a copper gauge that matches the breaker and keeps the voltage drop low on long runs.

Common breaker and wire sizes

BreakerCopper wire (NM-B)Typical use
15 A14 AWGLighting, general outlets
20 A12 AWGKitchen and bathroom outlets, laundry
30 A10 AWGElectric dryer, water heater
40 A8 AWGElectric range, cooktop
50 A6 AWGRange, EV charger, subpanel
60 A4 AWGSubpanel, large EV charger

Sizes follow the usual residential practice based on NEC ampacity rules (NEC 240.4(D) limits 14, 12 and 10 AWG copper to 15, 20 and 30 A). Voltage drop uses VD = 2 x K x I x L / circular mils, with K = 12.9 for copper. Conditions such as conduit fill, high ambient temperature or continuous loads can require a larger wire.

Safety: this tool is for planning. Electrical work must follow the National Electrical Code as adopted in your area, often requires a permit, and is best done by a licensed electrician.

Common questions

What size wire for a 20 amp circuit?

12 AWG copper. 14 AWG is only allowed on 15 A circuits. On a long run, the voltage drop may call for 10 AWG.

What is an acceptable voltage drop?

The National Electrical Code recommends, in an informational note, no more than 3% on a branch circuit and 5% in total from the service to the farthest outlet. It is a recommendation for efficiency, not a mandatory rule.

Does this work for aluminum wire?

This calculator assumes copper. Aluminum needs a larger gauge for the same current, typically two sizes larger, and connectors rated for aluminum.