Wire size calculator
Pick a copper gauge that matches the breaker and keeps the voltage drop low on long runs.
Common breaker and wire sizes
| Breaker | Copper wire (NM-B) | Typical use |
|---|---|---|
| 15 A | 14 AWG | Lighting, general outlets |
| 20 A | 12 AWG | Kitchen and bathroom outlets, laundry |
| 30 A | 10 AWG | Electric dryer, water heater |
| 40 A | 8 AWG | Electric range, cooktop |
| 50 A | 6 AWG | Range, EV charger, subpanel |
| 60 A | 4 AWG | Subpanel, large EV charger |
Sizes follow the usual residential practice based on NEC ampacity rules (NEC 240.4(D) limits 14, 12 and 10 AWG copper to 15, 20 and 30 A). Voltage drop uses VD = 2 x K x I x L / circular mils, with K = 12.9 for copper. Conditions such as conduit fill, high ambient temperature or continuous loads can require a larger wire.
Safety: this tool is for planning. Electrical work must follow the National Electrical Code as adopted in your area, often requires a permit, and is best done by a licensed electrician.
Common questions
What size wire for a 20 amp circuit?
12 AWG copper. 14 AWG is only allowed on 15 A circuits. On a long run, the voltage drop may call for 10 AWG.
What is an acceptable voltage drop?
The National Electrical Code recommends, in an informational note, no more than 3% on a branch circuit and 5% in total from the service to the farthest outlet. It is a recommendation for efficiency, not a mandatory rule.
Does this work for aluminum wire?
This calculator assumes copper. Aluminum needs a larger gauge for the same current, typically two sizes larger, and connectors rated for aluminum.